Control Voltage: 115 Volts AC +/- 10%
AC Drive Voltage: 115 VAC, 230 VAC, 460 VAC
+/- 10%
Max AC Input Current: 16/10/4 Amperes AC
DC Drive Voltages: 115 VAC, 230 VAC +/- 10%
Max AC Load Current: 12 RMS Amperes
Command:
4 to 20 Milliamperes
10 to 50 Milliamperes
For other inputs
consult factory.
Feedback:
0 to 1000 ohm
potentiometer
For other feedback
signals sonsult factory.
0 to +/- 5 or +/- 10 Volts DC drive command
signal.
Acuracy better than 0.7% over
temperature range.
Dead band: No command dead band in run to
position.
When at position dead band is
automatically enabled for noise immunity.
Signal Change to initiate control voltage
0.5 to 3.5 milliampers
Regulated 10 Volts DC (.1%) for the Position
Feedback Potentiometer
(1000 Ohms).
4 to 20 Milliamperes position current output.
Open, Close, enable relay contact outputs.
Monitor Relay contact output.
Operating Temperature: -20 to +70 deg.
C
Storage Temperature: -40 to 125 deg. C
Relative Humidity: 0 to 95%